MODBUS I/O modules

>> For more information visit our new website www.sah.co.rs <<

                     

   

Digital extensions modules - Modbus RTU communication (RS485)

   
MA16PX MA8PX8YR MA16YR

16 digital inputs (PNP)

8 digital inputs (PNP) 8 relay outputs

16 relay outputs

     
Analogue extensions modules - Modbus RTU communication (RS485)
                  
MA-4AD2DA MA-8AD-V
4 x 12bit analog inputs and 2 x 10bit analog outputs 8 x 12bit analog inputs
PID function PID funkcija
MA-6PT-P MA-6TCK-P
6 x Pt-100 temperature probe 6 x K type temperature probe
PID function PID function
                         
MANUAL
                      

Instruction Manual for Digital and Analog MA modules

                  

 

MA-8PX8YR 

8 digital inputs (PNP 24VDC) i 8 relay outputs

Electrical input specification

Input signal’s voltage

24VDC±10%

Input signal’s current

7mA 24VDC

Input ON current

> 4.5mA

Input OFF current

< 1.5mA

Input response time

<10ms

Input signal’s format

NPN ili PNP

Circuit insulation

Photo-electricity coupling insulation

Input action’s display

LED

Electrical relay output specifications

Interior power

AC250V, DC30V

Circuit insulation

Mechanism insulation

Action denote

LED

Max resistant load

3A

Max Induce load

80VA

Max Lamp load

100W

Minimal load

2mA 5VDC

Response time OFF→ON

10ms

Response time ONOFF

10ms

Insatllation

M3 screws or 35mm rail DIN46277

Back To Top ▲

              

MA-16PX

16 digital inputs (PNP 24VDC)

Electrical input specification

Input signal’s voltage

24VDC±10%

Input signal’s current

7mA 24VDC

Input ON current

> 4.5mA

Input OFF current

< 1.5mA

Input response time

<10ms

Input signal’s format

NPN ili PNP

Circuit insulation

Opto izolacija

Input action’s display

Da

Insatllation

M3 screws or 35mm rail DIN46277

Back To Top ▲
    

MA-16YR

16 Relejnih izlaza

Electrical output specification

Outupt voltage

AC250V, DC30V

Circuit insulation

Mechanism insulation

Action denote

LED

Max resistant load

3A

Max Induce load

80VA

Max Lamp load

100W

Minimal load

2mA 5VDC

Response time  OFF→ON

10ms

Response time  ONOFF

10ms

Insatllation

M3 screws or 35mm rail DIN46277

Back To Top ▲

 

MA-4AD2DA

4 x 12bit analog inputs   (0~5VDC, 0~10VDC selectable or 0~20mA,4~20mA selectable)

2 x 10bit analog outputs (0~5VDC, 0~10VDC selectable or 0~20mA,4~20mA selectable)

PID function

Analog input

Analogni output

Voltage

Current

Voltage Current

Analog input range

0~5 ili 0~10 VDC

0~20 ili 4~20mA

0~5 ili 0~10V

0~20 ili 4~20 mA

Conversion

12 bit

10 bit

Conversion speed

20 ms per channel

3 ms per chanenel

Integrated precision

0,8%

Power supply for analog

DC24V±10%,100mA

Installation

Use M3 screw or fix on DIN46277 rail ( width 35mm )

Back To Top ▲

      

    

MA-8AD-V

8 x 12bit analog inputs with PID function

Analog input range

0~5VDC ili 0~10VDC selectable

Analog input range

±18V

Conversion

12 bit

Conversion speed

20 ms per channel

Integrated precision

0,8%

Power supply

DC24V±10%,100mA

Installation

Use M3 screw or fix on DIN46277 rail ( width 35mm )

Back To Top ▲

 

         

MA-6PT-P

6 x Pt-100 temperature probe with  PID function

Temperature range

-100~350oC

Format data

-1000 ~ 3500, 12bit with sign

Precision

±0,1oC

Resolution

0,1oC

Conversion speed

20 ms per channel

Power supply

DC24V±10%,100mA

Installation

Use M3 screw or fix on DIN46277 rail ( width 35mm )

Back To Top ▲

 

MA-6TCK-P

6 x K type temperature probe with  PID function

Temperature range

0~1000oC

Format data

0~4095, 12 bit with sign

Precision

1oC

Conversion speed

20 ms per channel

Power supply

DC24V±10%,100mA

Installation

Use M3 screw or fix on DIN46277 rail ( width 35mm )