Phase protection

  

>> For more information visit our new website www.sah.co.rs <<

   

 

Phase supply control  (presence detection , rotational direction, asymmetry)

RSTB

Instruction Manual

3 phase supply control relay (Phase sequence relay) is designed to monitor 3 phase supplies and to protect motors and other loads against the faults listed below.

  •     Monitoring of rotational direction of phases

  •     Detection of complete failure of one or more of the phases

  •     Undervoltage detection (-10%)

  •     Overvoltage detection (+10%)

  •     Detection of phase asymmetry (imbalance) (±10%)

  •     Adjustable time delay from 0.1s to 10s

  •     SPDT 10A 250VAC(Resistive load) switch

The relay operates if any of the conditions occurs.

The relay releases if any of the conditions fails.

There is a Time Delay between the relay action and the condition occurs (except rotational direction of phases error ) to avoid very short interruptions or other momentary failures.
A selector switch allows selection of an adjustable time delay from 0.1s to 10s.
When the supply returns towards its rated value, the relay is re-energised according to the hysteresis value (5%).

Technical characteristics

Output Relay

NO and NC 10A 250VAC

Power Supply

3 phase 350~450VAC 50/60Hz

Mechanical Life

10.000.00 operations

Electrical Life

100.00 operations at rated load

Ambient temperature

-10 do +60 oC

Ambient humidity

45~85%RH

Mounting

At DIN rail

Indications

Green LED indicates relay state

Red LED indicates fault

Example and Operation Chart

Asymmetry 10%, main supply voltage 400VAC

Relay de-energisation threshold 400V * (100% - 10%) = 360V

Relay re-energisation threshold 400V * (100% - 5%) = 380V