Variable frequency drivers EDS-1000

>> For more information visit our new website www.sah.co.rs <<

 

Main Features

Models

Adequate Braking Resistors

Mounting sizes

Panel Dimensions Failure types

Instruction Manual V3.0

Instruction Manual V4.0

              

 

Main Features
Item Item description
Input Rating volt., frequency   3 phase 690V grade, 3 phase 690V ,50Hz/60Hz
3 phase 380V grade, 3 phase 380V ,50Hz/60Hz
1 phase 220V grade, 1 phase 220V ,50Hz/60Hz
Allowed work volt. range   3 phase 690 V grade: 586V~760V
3 phase 380 V grade: 320V~460V
1 phase 220V grade: 200V~260V
Output Voltage 690V grade: 0~690V; 380V grade: 0~380V; 200V grade: 0~220V 
Frequency From 0Hz to 400Hz
Over loading capacity 

G type: 150% of rating current for 1 minute, 200% of rating current for 0.5 second

P type:  120% of rating current for 1 minute

Control
performance
Control mode  Speed sensor less slip vector control, open loop V/F control 
Speed regulation range   1 : 100
Start-up torque   150% of rating torque at 1 Hz frequency  
Running speed stable state precision  ≤±0.5% of rating synchronous speed  
Frequency precision 

Digital setting: max. frequency x ± 0.01%

Analog setting: max.frequency x ± 0.5%

Frequency
resolution
Analog setting  0.1% of max. frequency 
Digital setting  precision : <100Hz  0.01Hz ; ≥100hz: 0.1Hz
Exterior impulse  0.5% of max. frequency 
Torque boost  Automatic torque boost, manual torque boost 0.1%~12.0% 
V/F curve (volt. frequency characteristic)  Set rating frequency randomly at range of 5~400Hz, can choose constant torque, digressive torque 1, digressive torque 2, digressive torque 3 and user-defined V/F in total 5 kinds of curve
Accelerating decelerating curve   2 modes: straight line accelerating decelerating and S curve accelerating decelerating; 7 kinds of accelerating decelerating time (unit minute/second can be optioned), max. time 6000 minutes.
Brake Power consumption brake  Interior or exterior brake resistance. 690 V grade haven’t build-in brake unit.
DC brake  Optional start-up and stop action frequency 0~15Hz action volt. 0~15% action time 0~20.0s 
Jog Jog frequency range: 0.50Hz~50.00Hz; jog accelerating decelerating time 0.1~60.0s can be set
Multi section speed running  Realized by interior PLC or control terminal  
Interior PID controller  Be convenient to make closed-loop system 
Automatic energy save running  Optimize V/F curve automatically based on the load to realize power save running 
Automatic volt. regulation AVR Can keep constant output volt. When power source voltage varies.
Automatic current limiting   Limit running current automatically to avoid frequent over-current which will cause trip
Running Function Running order specified channel  Key pad specified, control terminal specified, serial port specified 
Running frequency specified channel   Digital provision, analog provision, impulse provision, serial port provision, combined provision, can be switched at any time by kinds of method
Pulse output channel  Impulse square wave signal output of 0~20KHz can realize output of physical parameter such as setting frequency, output frequency etc. 
Analog output channel 2 channel of analog signal output, thereinto AO1 channel can be 4~20mA or 0~10V and AO2 channel is 0~10V; through them the inverter can realize output of physical parameter such as setting frequency, output frequency etc. 
Keypad LED display  Can display setting frequency, output frequency, output voltage, output current etc. 
Lock the button  Lock all or part of the buttons(analog potentiometer can’t be locked) 
Protection function Over-current protection, over-voltage protection, lack-voltage protection, over-heat protection, over-load protection, etc.
Ambient Use ambient  Indoor, not bare to sunlight, no dust, no corrosive gas, no flammable gas, no oil fog, no vapor, no water drop or salt etc.
Altitude Lower than 1000m ,if higher than 1000m, need to reduce amount  to use.
Ambient temperature -10ºC~+40ºC (under ambient temperature 40ºC ~50ºC, please reduce the volume or strengthen heat sink) 
Ambient humidity  Smaller than 95%RH, no condensation water 
Vibration Smaller than 5.9m/s²(0.6g) 
Storage temperature  -40~+70oC
Configuration Defending grade  IP20
Cooling mode  By fan with automatic temperature control 
Mounting mode Wall hanging 
Back To Top

 

 Models

NOTE
G type: General Purpose   P type: Pumps and Fans
VFDs Output Current(A) Power (KW) Impult Voltage Output
EDS1000 – 2S0015 7.5 1,5 200~260 VAC 3 x 220 VAC
EDS1000 – 2S0015C
with braking resistor
7.5 1,5
EDS1000 – 2S0022 10 2.2
EDS1000 – 2S0037 17 3.7
EDS1000 - 4T0015G/0022P 3.7/5 1.5/2.2  3 x 320~460 VAC 3 x 380 VAC
EDS1000 - 4T0022G/0037P 5/8.5 2.2/3.7 
EDS1000 - 4T0037G/0055P 8.5/13 3.7/5.5 
EDS1000 - 4T0055G/0075P 13/17 5.5/7.5
EDS1000 - 4T0075G/0110P 17/25 7.5/11
EDS1000 - 4T0110G/0150P 25/33 11/15
EDS1000 - 4T0150G/0185P 33/39 15/18.5
EDS1000 - 4T0185G/0220P 39/45 18.5/22
EDS1000 - 4T0220G/0300P 45/60 22/30
EDS1000 - 4T0300G/0370P 60/75 30/37
EDS1000 - 4T0370G/0450P 75/91 37/45
EDS1000 - 4T0450G/0550P 91/112 45/55
EDS1000 - 4T0550G/0750P 112/150 55/75
Additional option - RS485 MODBUS communication
Back To Top

 

 Adequate Braking Resistors

VFDs model

Breaking modul

Breaking resistor

Resistor power

EDS1000 – 2S0015

Not installed

70 Ω

400 W

EDS1000 – 2S0015C Built-in 70 Ω built-in 400 W

EDS1000 – 2S0022

Not installed

>= 50 Ω

600 W

EDS1000 – 2S0037

Not installed

>= 30 Ω

1000 W

EDS1000 – 4T0007

Built-in

>= 300 Ω

200 W

EDS1000 – 4T0015

Built-in

>= 300 Ω

200 W

EDS1000 – 4T0022G

Built-in

>= 300 Ω

200 W

EDS1000 – 4T0037G

Built-in

>= 125 Ω

400 W

EDS1000 – 4T0055G

Built-in

>= 80 Ω

650 W

EDS1000 – 4T0075G Built-in

>= 80 Ω

650 W
EDS1000 – 4T0110G Built-in

>= 50 Ω

1000 W
EDS1000 – 4T0150G Built-in >= 50 Ω 1000 W

Look at the list of available models for braking resistors

Gore ▲

Mounting Sizes

Image A. Image B.
 
Image C. Image D.
   
Image E. Image F.
   

VFD Type
G : General Purpose  

P : Pumps and Fans

A
(mm)

B
(mm)

W
(mm)

H
(mm)

D
(mm)

D1
(mm)

Fixing aperture
(mm)

Gross weight
kg.

Image

EDS100-2S004

EDS1000-4T0007G

110

160

125

170

123.2

135.5

4

1.5

A

EDS1000-2S0007

EDS1000-4T0015G

EDS1000-2S0015

EDS1000-4T0022P

EDS1000-2S0022

140

215

155

230

155

164

5

3.5

B

EDS1000-2S0037

EDS1000-4T0022G/0037P

EDS1000-4T0037G/0055P

EDS1000-4T0055G/0075P

EDS1000-4T0075G/0110P

185

275

200

290

178

187

6

6.1

B

EDS1000-4T0110G/0150P
EDS1000-4T0150G/0185P 135 330 218 345 210 221 7 10 C
EDS1000-4T0185G/0220P 180 410 260 430 252 261 9 17 C
EDS1000-4T0220G/0300P
EDS1000-4T0300G/0370P 200 485 280 505 252 261 9 22 C
EDS1000-4T0370G/0450P
EDS1000-4T0450G/0550P 250 620 370 645 258 267 12 50 C
EDS1000-4T0550G/0750P
EDS1000-4T0750G/0900P 400 790 590 820 372   12   D
EDS1000-4T0900G/1100P
Back To Top ▲

   

Panel Dimensions

 
Back To Top ▲

 

Failure type and the countermeasure

Failure code Failure type Possible reason Countermeasure
E001 Overcurrent during
accelerating process
Accelerating time is too short Prolong accelerating time
Improper V/F curve Adjust V/F curve setting,adjust
manual torque boost or change to
automatic torque boost
Restart rotating motor Set speed checking restart function
Low power source voltage Check input power supply
Too small power of the inverter Choose inverter with high-power
E002 Overcurrent during
decelerating process
Decelerating time is too short Prolong decelerating time
Have potential energy load or big inertia load Increase braking power of external
energy consumption braking
subassembly
Power of inverter is a bit small Choose inverter with high-power
E003
Overcurrent
during constant
speed process
Load change suddenly or have unwonted phenomena Check or reduce break of the load
Accel/Decel time is set to too short Prolong accelerating decelerating time properly
Low power source voltage Check input power supply
Power of inverter is a bit small Choose inverter with high-power
E004 Overvoltage
during
accelerating
process
Unwonted input voltage Check input power supply
Accel time is set to too short Prolong accelerating time properly
Restart rotating motor Set speed checking restart function
E005 Overvoltage
during
decelerating
process
Decelerating time is too short Prolong decelerating time
Have potential energy load or big
inertia load
Increase braking power of external  energy consumption braking subassembly
E006 Overvoltage
during constant
speed process
Unwonted input voltage Check input power supply
Accel/Decel time is set to too short Prolong accelerating decelerating time properly
Input voltage change abnormally Assemble reactor
Load inertia is a bit big Use energy consumption subassembly
E007 Inverter control
power supply 
overvoltage
Unwonted input voltage Check input power supply or look for service
E008 Inverter
overload
Accel time is set to too short Prolong accelerating time
DC injection braking is too big Reduce DC injection braking current,prolong braking time
Improper V/F curve Adjust V/F curve and torque boost
Restart rotating motor Set speed checking restart function
Power source voltage is too low Check power source voltage
Load is too big Choose inverter with high-power
E009 Motor overload Improper V/F curve Adjust V/F curve and torque boost
Power source voltage is too low Check power source voltage
General motor run at low speed with big load Can choose frequency conversion motor for long time low speed run
Motor overload protection factor set incorrectly To set motor overload protection factor correctly
Motor blocked up or load change too suddenly and quickly Check the load
E010 Inverter over
heating
Air-path blocked To clear air-path or improve ventilation condition
Ambient temperature is too high Improve ventilation condition, lower carrier frequency
Fan damaged Replace the fan
E011 Reserved Reserved Reserved
E012 Reserved Reserved Reserved
E013 Inverting module protection Transient overcurrent of the inverter Refer to countermeasure for overcurrent
Phase to phase short circuit or earthing short circuit of output 3 phase Wiring again
Air-path blocked or fan damaged To clear air-path or replace the fan
Ambient temperature is too high Lower ambient temperature
Connecting wire or insert on control board loose Check and connect the wire again
Unwonted control wave caused by missing output phase etc. Check wiring
Assistant power supply damaged and drive voltage lacking Look for service from manufacturer or agent
Unwanted control board Look for service from manufacurer or agent
E014 External device
failure
Use sudden stop key (STOP) in non-keypad run mode Look up operation mode
Use sudden stop key (STOP) under condition of stall Set running parameter correctly
Sudden stop terminal for external failure closed Open external failure terminal after external failure is settled
E015 Current
detecting circuit
failure
Connecting wire or insert on control board loose Check and connect the wire again
Assistant power supply damaged Look  for  service  from  manufacturer or agent
Hall component damaged Look  for  service  from  manufacturer or agent
Unwonted amplifying circuit Look for service from manufacturer or agent
E016 RS485
communication
failure
Baud rate set improperly Set Baud rate properly
Serial port communication error Press STOP/RESET key to reset,look for service
Failure warning parameter set improperly Modify F2.16, F2.17
Upper device doesn’t work Check if upper device work and wiring is correct
E017 Reserved Reserved Reserved
E018 Reserved Reserved Reserved
E019 Under voltage
failure
Under voltage Check spot input voltage
E020 System disturbance Serious disturbance Reset by pressing STOP/RESET key or add mains filter at power supply input side
Main control DSP read and write wrongly Reset by the key-press, look for service
E021 Reserved Reserved Reserved
E022 Reserved Reserved Reserved
E023 E²PROM read and write wrongly Mistake take place when read or write control parameter Reset by pressing STOP/RESET, look for service from manufacturer or agent
P.OFF Under vlotage Under vlotage Check spot input voltage