Variable frequency drivers EDS-2000

>> For more information visit our new website www.sah.co.rs <<

                

Main Features Models
Mounting Sizes Panel Dimensions
Instruction Manual
Failure types

                

 

Main Features
Item Item description
Input Rating volt., frequency 3 phase 380V ,50Hz/60Hz
Allowed work volt. range 3 x 320~460V
Output Voltage 0~380V
Frequency From 0Hz to 400Hz
Over loading capacity G type : 150% of rating current for 1 minute
          200% of rating current for 0.5 second
P type : 3.7~132KW 120% of rating current for 1 minute
          160KW above: 110% of rating current for 1 minute
          150% of rating current for 1 second
EDS2800 type:
150% of rating current for 3 minutes
          200% of rating current for 5 second
Control
performance
Control mode Optimized space volt, vector PWM control mode for EDS2000; simple current vector mode for EDS2800 series
Speed regulation range 1 : 100
Start-up torque 150% of rating torque at 3Hz frequency for EDS2000; 130% of rated torque at 1Hz frequency for EDS2800 series
Running speed stable state precision ≤±0.5% of rating synchronous speed
Frequency precision

Digital setting: max. frequency x ± 0.01%

Analog setting: max.frequency x ± 0.2%

Frequency
resolution
Analog setting 0.1% of max. frequency
Digital setting 0.01 Hz
Exterior impulse 0.5% of max. frequency

Keypad digital setting 0.01 Hz
Torque boost Automatic torque boost, manual torque boost 0.1%~20.0%
V/F curve (volt. frequency characteristic) Set rating frequency randomly at range of 5~400Hz, can choose constant torque, digressive torque 1, digressive torque 2, digressive torque 3 and user-defined V/F in total 5 kinds of curve
Accelerating decelerating curve 3 modes: straight line accelerating decelerating, S curve accelerating decelerating and automatic accelerating decelerating mode; 4 kinds of accelerating decelerating time (unit minute/second can be optioned), max. time 6000 minutes.
Brake Power consumption brake Interior or exterior brake resistance
  DC brake  Optional start-up and stop action frequency 0~15Hz action volt. 0~15% action time 0~20.0s
Jog Jog frequency range: 0.50Hz~50.00Hz; jog accelerating decelerating time 0.1~60.0s can be set
Multi section speed running Realized by interior PLC or control terminal
Interior PID controller Be convenient to make closed-loop system
Automatic energy save running Optimize V/F curve automatically based on the load to realize power save running
Automatic volt. regulation AVR Can keep constant output volt. When power source voltage varies.
Automatic current limiting Limit running current automatically to avoid frequent over-current which will cause trip
Running Function Running order specified channel Key pad specified, control terminal specified, serial port specified
Running frequency specified channel Digital provision, analog provision, impulse provision, serial port provision, combined provision, can be switched at any time by kinds of method
Pulse output channel Impulse square wave signal output of 0~50KHz can realize output of physical parameter such as setting frequency, output frequency etc. 
Analog output channel 2 channel of analog signal output, optional 4~20mA or 0~10V separately; can realize output of physical parameter such as setting frequency, output frequency etc. 
Special channel for EDS2800 Inter-insulated 2 channel of 0~1A and 2 channel of 0-10V analog input signal
Keypad LED display Can display setting frequency, output frequency, output voltage, output current etc. in total 20 kinds of parameter
LCD display Optional, operation is noted by English
Parameter copy Use keypad and remote-control keypad to copy the parameter speedily
Lock the button Lock all the button
Protection function Over-current protection, over-voltage protection, lack-voltage protection, over-heat protection, over-load protection, missing phase protection (in option) etc.
Fitting parts LCD keypad, brake subassembly, remote control keypad, conecting cable for remote-control keypad etc.
Ambient Use ambient  Indoor, not bare to sunlight, no dust, no corrosive gas, no flammable gas, no oil fog, no vapor, no water drop or salt etc.
Altitude Lower than 1000m
Ambient temperature -10ºC~+40ºC (under ambient temperature 40ºC ~50ºC, please reduce the volume or strengthen heat sink) 
Ambient humidity Smaller than 95%RH, no condensation water
Vibration Smaller than 5.9m/s²(0.6g)
Storage temperature -40~+70oC
Configuration Defending grade  IP20
Cooling mode By fan with automatic temperature control
Mounting mode Wall hanging for type of 132kwG/160kWP and below, cabinet standing for type of 160kwG/200kwP and above, wall hangning for all EDS28000 types
Back To Top ▲
                                                    

Models

Inverter Type

Output Current(A)

Power (KW)

Impute voltage

Output

EDS 2000-4T0750G/0900P

150/176

75/90 KW

3 x 320-460 VAC 3 x 380 VAC
EDS 2000-4T0900G/1100P 176/210

90/110 KW

Additional option - RS485 MODBUS communication

Back To Top ▲

                                 

Mounting Sizes
Image A. Image B. 
   
Image C. Image D.
   
Inverter Model

A

(mm)

B

(mm)

W

(mm)

H

(mm)

D
(mm)
D1
(mm)

Fixing aperture

(mm)

Image

EDS 2000-4T0022G/0037P

140 

215

155

230 155 164

A

EDS 2000-4T0037G/0055P
EDS 2000-4T0055G/0075P 185  275 200  290 178 187 6
EDS 2000-4T0075G/0110P
EDS 2000-4T0110G/0150P  140 350 230 370 212 223 7 B
EDS 2000-4T0150G/0850P  
EDS 2000-4T0185G/0220P 180  440 260 460 252 261 9
EDS 2000-4T0220G/0300P
EDS 2000-4T0300G/0370P 200 515 300 535 252 261
EDS 2000-4T0370G/0450P
EDS 2000-4T0450G/0550P  250 620 370 645 258 267 12
EDS 2000-4T0550G/0750P
EDS 2000-4T0750G/0900P
EDS 2000-4T0900G/1100P  300 650 480 680 360 369
EDS 2000-4T1100G/1320P  400 720 480 750 372 381
EDS 2000-4T1320G/1600P 
EDS 2000-4T1600G/2000P  -- -- 600 1500 500 --
C
Back To Top

 

Panel Dimensions
Back To Top

 

Failure type and the countermeasure

Failure code Failure type Possible reason Countermeasure
E001 Overcurrent during
accelerating process
Accelerating time is too short Prolong accelerating time
Improper V/F curve Adjust V/F curve setting,adjust
manual torque boost or change to
automatic torque boost
Restart rotating motor Set speed checking restart function
Low power source voltage Check input power supply
Too small power of the inverter Choose inverter with high-power
E002 Overcurrent during
decelerating process
Decelerating time is too short Prolong decelerating time
Have potential energy load or big inertia load Increase braking power of external
energy consumption braking
subassembly
Power of inverter is a bit small Choose inverter with high-power
E003
Overcurrent
during constant
speed process
Load change suddenly or have unwonted phenomena Check or reduce break of the load
Accel/Decel time is set to too short Prolong accelerating decelerating time properly
Low power source voltage Check input power supply
Power of inverter is a bit small Choose inverter with high-power
E004 Overvoltage
during
accelerating
process
Unwonted input voltage Check input power supply
Accel time is set to too short Prolong accelerating time properly
Restart rotating motor Set speed checking restart function
E005 Overvoltage
during
decelerating
process
Decelerating time is too short Prolong decelerating time
Have potential energy load or big
inertia load
Increase braking power of external  energy consumption braking subassembly
E006 Overvoltage
during constant
speed process
Unwonted input voltage Check input power supply
Accel/Decel time is set to too short Prolong accelerating decelerating time properly
Input voltage change abnormally Assemble reactor
Load inertia is a bit big Use energy consumption subassembly
E007 Inverter control
power supply 
overvoltage
Unwonted input voltage Check input power supply or look for service
E008 Inverter
overload
Accel time is set to too short Prolong accelerating time
DC injection braking is too big Reduce DC injection braking current,prolong braking time
Improper V/F curve Adjust V/F curve and torque boost
Restart rotating motor Set speed checking restart function
Power source voltage is too low Check power source voltage
Load is too big Choose inverter with high-power
E009 Motor overload Improper V/F curve Adjust V/F curve and torque boost
Power source voltage is too low Check power source voltage
General motor run at low speed with big load Can choose frequency conversion motor for long time low speed run
Motor overload protection factor set incorrectly To set motor overload protection factor correctly
Motor blocked up or load change too suddenly and quickly Check the load
E010 Inverter over
heating
Air-path blocked To clear air-path or improve ventilation condition
Ambient temperature is too high Improve ventilation condition, lower carrier frequency
Fan damaged Replace the fan
E011 Reserved Reserved Reserved
E012 Reserved Reserved Reserved
E013 Inverting module protection Transient overcurrent of the inverter Refer to countermeasure for overcurrent
Phase to phase short circuit or earthing short circuit of output 3 phase Wiring again
Air-path blocked or fan damaged To clear air-path or replace the fan
Ambient temperature is too high Lower ambient temperature
Connecting wire or insert on control board loose Check and connect the wire again
Unwonted control wave caused by missing output phase etc. Check wiring
Assistant power supply damaged and drive voltage lacking Look for service from manufacturer or agent
Unwanted control board Look for service from manufacurer or agent
E014 External device
failure
Use sudden stop key (STOP) in non-keypad run mode Look up operation mode
Use sudden stop key (STOP) under condition of stall Set running parameter correctly
Sudden stop terminal for external failure closed Open external failure terminal after external failure is settled
E015 Current
detecting circuit
failure
Connecting wire or insert on control board loose Check and connect the wire again
Assistant power supply damaged Look  for  service  from  manufacturer or agent
Honeywll component damaged Look  for  service  from  manufacturer or agent
Unwonted amplifying circuit Look for service from manufacturer or agent
E016 RS485
communication
failure
Baud rate set improperly Set Baud rate properly
Serial port communication error Press STOP/RESET key to reset,look for service
Failure warning parameter set improperly Modify F2.19, F2.20 and F9.12
Upper device doesn’t work Check if upper device work and wiring is correct
E017 Reserved Reserved Reserved
E018 Reserved Reserved Reserved
E019 Lacking voltage
failure
Lacking voltage Check spot input voltage
E020 System disturbance Serious disturbance Reset by pressing STOP/RESET key or add mains filter at power supply input side
Main control DSP read and write wrongly Reset by the key-press, look for service
E021 Reserved Reserved Reserved
E022 Reserved Reserved Reserved
E023 E²PROM read and write wrongly Mistake take place when read or write control parameter Reset by pressing STOP/RESET, look for service from manufacturer or agent
P.OFF Lacking voltage
failure
Lacking voltage Check spot input voltage